beautypg.com

3 grid fault, Grid fault – SMA SC 250U User Manual

Page 36

background image

Error Diagnosis

SMA America, LLC

36

SCUS-BE-BUS120514

User Manual

7.1.3 Grid Fault

If the fault is on the grid side, a two-digit error code appears
on the right side of the system display (see figure to the right:
A). With this error number you can narrow down the type of
malfunction. The table below describes the type of fault, its
cause and what you can do to rectify the fault.

77

Error text:
Device fault
Cause of fault:
Contactor defective.
Corrective measures:

• Contact the SMA Serviceline.

78

Error text:
Surge voltage arrestor failure
Cause of fault:
Surge error.
Corrective measures:

• Check surge voltage arrestor.

79

Error text:
Reverse current failure
Cause of fault:
Short circuit in the PV generator.
Corrective measures:

• Check the PV generator for short circuits.

No.

Description

01

Error text:
Grid fault
Cause of fault:
The grid voltage is too high.
Corrective measures:

• Check the grid voltage.
• If the grid voltage lies outside the acceptable range because of local grid conditions,

ask the grid operator if the voltages can be adjusted at the feed-in point.

No.

Description

This manual is related to the following products: