beautypg.com

7 connecting the sensor to the sunny central, Connecting the sensor to the sunny central – SMA PT100U-NR User Manual

Page 14

background image

Installation and Electrical Connection

SMA Solar Technology AG

14

PT100UNR-IEN083510

Installation Guide

4.7 Connecting the Sensor to the Sunny Central

The sensor is connected to the Sunny Central using the =Z5-X5 terminal strips.

4-wire system

2-wire system

or

or

Realizing the electrical connection
The wiring diagram provided must be used for establishing the electrical connections and
connectors.

Connecting the PT100 temperature sensor to "=Z5-X5" in a 4-wire system

I+ at the sensor

Terminal 1

V+ at the sensor

Terminal 2

I- at the sensor

Terminal 3

V- at the sensor

Terminal 4

Connecting the PT100 temperature sensor to "=Z5-X5" in a 2-wire system

V+ at the sensor

Bridge terminal 1 with terminal 2

V- at the sensor

Bridge terminal 3 with terminal 4

Connecting the PT100 temperature sensor to "=Z5-X5" in a 2-wire system

V+ at the sensor

Terminal 5

V- at the sensor

Terminal 6

Connecting the PT100 temperature sensor to "=Z5-X5" in a 2-wire system

V+ at the sensor

Terminal 7

V- at the sensor

Terminal 8