Page 21: Control voltage is present

background image

SMA Solar Technology AG

6  Maintenance when Medium Voltage, Low Voltage and Control Voltage Is Present

Maintenance manual

TCS-CP-WH-en-10

21

6 Maintenance when Medium Voltage, Low Voltage

and Control Voltage Is Present

6.1 Checking that Transformer Fan Works

1. Set thermostat to the minimum value.
2. Check whether the transformer fan starts.

If the transformer fan does not start, contact the SMA Service Line.

3. Reset the thermostat to the initial value. The initial value is included in the circuit diagram.

6.2 Checking Exterior of Steel Station for Damage

Required maintenance material (not included in the scope of delivery):

☐ Touch-up sticks, brushes or cans of spray paint or, alternatively, 2K-PUR acrylic paint in the

appropriate RAL colour can be used to repair minor surface damage such as corrosion.
Observe the relevant instructions of the paint manufacturer.

☐ Touch-up paint or 2K-PUR acrylic paint in the appropriate RAL colour can be used to repair

large-area surface damage such as corrosion. Observe the relevant instructions of the paint
manufacturer.

☐ Abrasive cloth
☐ Degreaser
☐ Wire brushes
☐ Brush attachments for drill and angle grinder
☐ Orbital sander

%"/(&3

High voltages are present in the Transformer Compact Station. Failure to adhere to the
safety messages will lead to death or serious injuries as a result of electric shock.

• Wear personal protective equipment.
• Do not touch any live components of the Transformer Compact Station or the medium-voltage

grid.

• Comply with all applicable safety regulations for handling medium-voltage grids.

Position

RAL colour

Colour scheme

Roof

RAL 7004

Signal grey

Base

RAL 7005

Mouse grey

Enclosure

RAL 9016

Traffic white