3  Maintenance Schedule

SMA Solar Technology AG

12

TCS-CP-WH-en-10

Maintenance manual

1 year

Medium-voltage
transformer

• Check oil level
• Check oil temperature
• Check transformer for oil leaks
• You should switch the tap changer to a

voltage-free state at least once per year with ten
switching cycles in each case across the entire
range. This will prevent oil and carbon deposits
from accumulating on the converter contacts

• Check the paint and the sealing joints of

transformers not currently in operation

• Carry out a check for leaks, rust stains and

damage

• Check cable entries, protective devices, and

control elements for dirt

• Check for local warming as a result of transition

resistance at the overvoltage and undervoltage
connections

• Check the ambient temperature and the room

ventilation

• Check the transformer for operating noise
• Check the transformer protective devices/contact

thermometers and accessories
– Functionality
– Set and check the contacts
– Cabling

• Check the test device

Interval

Component

Activity