SMA TCS 500-SC Maintenance manual User Manual
Page 11
SMA Solar Technology AG
3 Maintenance Schedule
Maintenance manual
TCS-CP-WH-en-10
11
Interval
Component
Activity
If required
Concrete station
• Clean air inlets and outlets
Steel station
• Clean air inlets and outlets
Station sub-distribution
• Test residual-current device before using the socket
• Check the lighting
Medium-voltage
transformer
• Check sealing joints of the transformer and tighten
screws slightly if necessary
• Clean insulators
• Remove any rust stains and repaint
• Drain and refill oil
• Take oil samples
MV switchgear*
• Clean interior
• Clean enclosure
• Clean surfaces
• Check screw connections
• Check cable connections
• Check fuses or circuit breakers
• Check measuring instruments
MV transformer
protection device from
Automation 2000
• Take oil samples
• Carry out a gas discharge
• Carry out an overpressure test
• Test thermostat
Low-voltage meter (GSE)
from Landis+Gyr AG**
• Change battery
Interval
depends on
national
regulations
and
standards
Low-voltage meter (GSE)
from Landis+Gyr AG
• Check optical test output
• Carry out creep test
• Check active power measurement
• Check reactive power measurement