3  Maintenance Schedule

Maintenance manual

TCS-CP-WH-en-10

11

Interval

Component

Activity

If required

Concrete station

• Clean air inlets and outlets

Steel station

• Clean air inlets and outlets

Station sub-distribution

• Test residual-current device before using the socket
• Check the lighting

Medium-voltage
transformer

• Check sealing joints of the transformer and tighten

screws slightly if necessary

• Clean insulators
• Remove any rust stains and repaint
• Drain and refill oil
• Take oil samples

MV switchgear*

• Clean interior
• Clean enclosure
• Clean surfaces
• Check screw connections
• Check cable connections
• Check fuses or circuit breakers
• Check measuring instruments

MV transformer
protection device from
Automation 2000

• Take oil samples
• Carry out a gas discharge
• Carry out an overpressure test
• Test thermostat

Low-voltage meter (GSE)
from Landis+Gyr AG**

• Change battery

Interval
depends on
national
regulations
and
standards

Low-voltage meter (GSE)
from Landis+Gyr AG

• Check optical test output
• Carry out creep test
• Check active power measurement
• Check reactive power measurement