4  Disconnecting from and Reconnecting to Voltage Sources

Maintenance manual

TCS-CP-WH-en-10

17

4.6 Reconnecting the Low Voltage

☐ Medium voltage is connected.

1. In case of a Transformer Compact Station with AC circuit breaker, switch on the AC circuit

breaker.

2. In case of a Transformer Compact Station without AC circuit breaker, switch on the AC circuit

breaker in the inverter and switch on the inverter.

4.7 Reconnecting the Control Voltage

1. Open station sub-distribution.
2. Switch on all miniature circuit-breakers and all residual-current devices.
3. Switch on the transformer for auxiliary power supply, if present.