9.5 Transformer Compact Station 1250SC
Medium-voltage side
Low-Voltage Side
Dimensions and Weight
Climatic Conditions
Rated power (@ 25°C)
P
ACnom
1 375 kVA
AC nominal power (@ 45°C)
P
AC
1 250 kVA
AC nominal voltage
V
ACnom
15 kV / 20 kV
AC voltage range
V
AC
13.5 kV … 16.5 kV / 18 kV … 22 kV
Rated grid voltage
V
AC
20 kV
Rated grid frequency
f
AC
50 Hz
Nominal current
I
nom
36.4 A
Nominal input voltage
V
AC
315 V
Nominal input current
I
nom
2 x 1 155 A
Width x height x depth
with medium-voltage switchgear
3 280 mm x 2 550 mm x 2 500 mm
Width x height x depth
without medium-voltage switchgear
2 380 mm x 2 550 mm x 2 500 mm
Weight with medium-voltage switchgear
16.8 t
Weight without medium-voltage switchgear
12.4 t
Degree of protection
*
*
As per EN 60529
IP23
Operation temperature range
− 20°C … +45°C
Relative humidity, non-condensing
15% … 95%
Maximum operating altitude above sea level
(MSL)