3 transformer compact station 800sc, Transformer compact station 800sc – SMA TCS 500-SC User Manual
Page 32
9 Technical Data
SMA Solar Technology AG
32
TCS-IT-IEN103610
Installation Manual
Climatic Conditions
Options
9.3 Transformer Compact Station 800SC
Medium-voltage side
Low-Voltage Side
Operation temperature range
− 20°C … +45°C
Relative humidity, non-condensing
15% … 95%
Maximum operating altitude above sea level
(MSL)
1 000 m
Internal power supply transformer
*
*
Additional power classes available on request.
6 kVA
Medium-voltage switchgear
None / RE-T / C-C-T
Low-voltage switchgear
1 x LV/HRC switch-disconnector /
1 x circuit breaker
Pre-assembled cable set
5 m / 7.5 m / 10 m / 15 m
Communication distribution box
Communit
Low-voltage meter
GSE meter
Rated power (@ 25°C)
P
ACnom
880 kVA
AC nominal power (@ 45°C)
P
AC
800 kVA
AC nominal voltage
V
ACnom
15 kV / 20 kV
AC voltage range
V
AC
13.5 kV … 16.5 kV / 18 kV … 22 kV
Rated grid voltage
V
AC
20 kV
Rated grid frequency
f
AC
50 Hz
Nominal current
I
Nominal
23.1 A
Nominal Voltage
V
AC
360 V
Nominal voltage reduced by 2.5%
*
*
Can be set with on-load tap-changer in transformer
V
AC
351 V
Nominal voltage reduced by 5.0%
V
AC
342 V
Nominal voltage reduced by 7.5%
V
AC
333 V
Nominal voltage reduced by 10.0%
V
AC
324 V
Nominal voltage reduced by 12.5%*
V
AC
315 V
Nominal current
I
nom
1 283 A