2 connecting dc main cables to the busbar – SMA SSM8-21-BS User Manual
Page 28

6 Electrical Connection
SMA Solar Technology AG
28
SSMxx-21-IA-BS-JP-en-20
Installation Manual
6.5.2 Connecting DC Main Cables to the Busbar
Figure 12: Assembly of the connection with a ring terminal lug
Additionally required material (not included in the scope of delivery):
☐ Ring terminal lugs (size: for M12 screw)
☐ Clean cloth
☐ Ethanol cleaning agent
Procedure:
1. Strip off the DC main cable insulation.
2. Fit the DC main cables with ring terminal lugs.
3. Clean the contact surfaces using a clean cloth and ethanol cleaning agent. Do not touch the contact surfaces after
cleaning.
4. Connect the DC main cables in accordance with the circuit diagram (torque: 60 Nm). Only use the supplied
fastening material and connect a maximum of two adjacent DC main cables to each busbar.
5. Secure the DC main cables to the cable support rail.
Position
Designation
A
Screw M12
B
Spring washer
C
Fender washer
D
Tin-plated copper bar
E
Tin-plated ring terminal lug
F
Nut M12