7. Ensure that no voltage is present at the DC

inputs on the inverter using a suitable measuring
device.

8. Loosen the swivel nuts.
9. Loosen the screws of the connection cap and

remove the connection cap.

10. Use a suitable measuring device to check that no voltage is present at the AC connector

between L and N and between L and the grounding conductor. To do so, insert the test probe
(maximum diameter: 2 mm) into each round opening of the connecting terminal plate.

11. Release and disconnect the AC connector using

the sliders located on the side.

L N

1

1

2

2.2

Safety Information

This section contains safety information that must be observed at all times when working on or with
the product.
To prevent personal injury and property damage and to ensure long-term operation of the product,
read this section carefully and observe all safety information at all times.

2 Safety

SMA Solar Technology AG

Service Manual for Installers

SB15-25-SG-en-10

6