Event number

Message, cause and corrective measures

301

Grid fault
The ten-minute average value of the grid voltage is no longer within the per-
missible range. The grid voltage or grid impedance at the connection point is
too high. The inverter disconnects from the utility grid to maintain power qual-
ity.
Corrective measures:

• During the feed-in operation, check whether the grid voltage at the

connection point of the inverter is permanently in the permissible range.
If the grid voltage is outside the permissible range due to local grid
conditions, contact the grid operator. The grid operator must agree with
an adjustment of the voltage at the feed-in point or with a change of the
monitored operating limits.
If the grid voltage is permanently within the permissible range and this
message is still displayed, contact the Service (see Section 11 "Contact",
page 33).

302

Temperature AC voltage
The inverter has reduced its power due to a too-high grid voltage to ensure
grid stability.
Corrective measures:

• If possible, check the grid voltage and observe how often fluctuations

occur. If fluctuations occur frequently and this message is displayed often,
contact the grid operator and request approval to change the operating
parameters of the inverter. If the grid operator gives his approval, discuss
any changes to the operating parameters with Service (see Section 11
"Contact", page 33).

401 to 404

Grid fault
The inverter has disconnected from the utility grid. A stand-alone grid or a very
large change in the power frequency was detected.
Corrective measures:

• Check the grid connection for significant short-term frequency fluctuations.

4 Event Messages

SMA Solar Technology AG

Service Manual for Installers

11

SB15-25-SG-en-10