NOTE:

Galvanized pipe is desirable above the roofline
due to its higher corrosion resistance. Continue
to add pipe sections throughout the flashing
until the height of the vent cap meets the mini-
mum height requirements specified in Fig. 5. or
local codes.

For steep roof pitches, the vertical height must
be increased. A poor draft, or down drafting
can result in high wind conditions, trees or
neighbor's roof lines. In these cases, increas-
ing the height may solve a drafting problem.
REMEMBER to check that you are within the
maximum vertical height restrictions, and are
placing the appropriate vent restrictors as out-
lined in the venting chart within this manual.

Any storage spaces or closets which the vent
must pass through must be enclosed.

Flat to 7/12

2 Feet

0.61 Meters

Over 7/12-8/12

2 Feet

0.61 Meters

Over 8/12-9/12

2 feet

0.61 Meters

Over 9/12-10/12

2.5 Feet

0.76 Meters

Over 10/12-11/12

3.25 Feet

1.00 Meters

Over 11/12-12/12

4 Feet

1.22 Meters

Over 12/12-14/12

5 Feet

1.52 Meters

Over 14/12-16/12

6 Feet

1.83 Meters

Over 16/12-18/12

7 Feet

2.13 Meters

Over 18/12-20/12

7.5 Feet

2.29 Meters

Over 20/12-21/12

8 Feet

2.44 Meters

Roof Pitch

Minimum Vent Height

Vertical Termination Cap

Storm Collar

Flashing

Ceiling Firestop

Round Support Box /
Wall Thimble

Length of Pipe

Length of Pipe

SDA-U adaptor

VENTING - VERTICAL TERMINATION USING SIMPSON DURA-VENT PIPE ONLY

Typical Vertical venting

configuration using Simpson Dura-

Vent Direct Vent System

Simpson Dura-Vent venting

components are listed on page 22

Fig. 5

H-represents vent

height

H