AEC TCU Series Open Reservoir Water Temperature Control Units User Manual
Page 48

Open Resevoir Water Temperature Control Units
Page 49
Condition
Possible cause
Solution
Unit does not heat/cannot 
achieve set point. 
Defective heater contactor.
Visually inspect coil and 
contacts; repair/replace 
defective contactors. 
Defective immersion heater.
Check resistance on all three (3) 
legs of the heater with an ohm 
meter. If not all equal, contact 
factory for replacement heater. 
Controller heat output open.
Check the heater output with an 
ohm meter to ground. It should 
read in the mega-ohm range. 
Infinite or zero readings indicate 
a defective output. 
Heater contactor is not 
energizing, but HEAT LED is on. 
Set process temperature to 
maximum and check for control 
voltage at heater contactor. 
Immersion heater elements 
dirty. 
Remove heater and clean 
elements. 
Immersion heater element is 
burned out. 
Check heater tank for 
scorched/discolored paint. 
Check resistance on all three (3) 
legs of the heater with an ohm 
meter. Replace heater as 
required. 
Check for balanced amp draws, 
and supply voltage. If not 
present replace immersion 
heater. 
OUT1 indicator is on, but no 
voltage on heater contact. 
Replace relay board on 
controller. 
Cooling valve is leaking.
Dismantle valve and clean out.
Solenoid valve is not operating, 
but COOL LED is on. 
Set process temperature to 
minimum and check for 
magnetism on top of solenoid 
coil. 
Magnetism on coil.
Clean coil.
Faulty/dirty solenoid valve.
Press VENT button several 
times to flush the valve. 