5-5 Checking Motor Rotation Direction
Check for correct pump rotation direction by looking at the top of the motor. Press the
START
button and the
STOP
button, and note the direction that the motor turns.
Rotation should be clockwise when viewed from the motor end.
Make sure that a qualified electrician performs the following steps.
To change rotation direction:
§
Disconnect and lock out power at the fused disconnect.
§
Reverse any two incoming leads at the power terminal blocks.
§
Do not switch leads at the motor or motor starters.
5-6 Shutting Down the Temperature Control Unit
Cool the unit down by selecting a set point of zero (
0
). Let the unit stabilize at one
temperature close to the incoming water temperature, then press the
STOP
button.
Now rotate the disconnect switch to the
OFF
position.