Open Resevoir Water Temperature Control Units

5-3 Starting the Temperature Control Unit

You can also use these steps to AUTO-TUNE the Controller, and operate the Unit
with the Controller.

The Auto-Tune function lets you fine-tune the control PID to process requirements.
Activate the Auto-Tune function whenever the process under control changes. Don't
be alarmed by control response. It may take the process temperature above and below
the set points as many as three (3) times. It will then level off and control to the
process set point. Auto-tuning can take up to 45 minutes, and is best done before
any product is run.

1. Push the ON/OFF rocker switch to the ON ( | ) to energize the unit and begin the

temperature control cycle. The switch will be illuminated whenever the unit is on.

2. The unit will automatically vent for approximately one minute.
3. If needed, press and hold the vent button to purge any additional air from the process

loop.

4. Set process temperature (PV) by pressing the

Scroll key until SP1 appears in

the upper display. Then press the

Up Arrow or

Down Arrow keys to

adjust the setpoint.

5. If the unit does not maintain its process value, allow your process to reach the set

point temperature. Then Autotune the control by pressing the the

Scroll key

until SP1 appears in the upper display. Then press the

Up Arrow or

Down Arrow keys to activate the tune.