Figure 2 tcu series unit full-load amps – AEC TCU Series Open Reservoir Water Temperature Control Units User Manual
Page 19
Page 20
Open Resevoir Water Temperature Control Units
Figure 1
Typical Open Reservoir Water Temperature Control Unit and Specifications
Dimensions
Shipping
Pump
H
W
D
weight
460 / 230
hp
kW
gpm
lpm
psig
kPa
in.
cm
in. cm
in.
cm lbs.
Kg
9 kW heater
¾
0.56
30
114
25
172
54
138
18
46
36.5
93
310/
340
141/
155
1
0.75
35
133
30
207
2
1.50
50
190
30
207
3
2.25
60
227
40
276
5
3.75
75
284
54
372
340/
370
155/
168
7½
5.63
90
341
63
434
Figure 2
TCU Series Unit Full-Load Amps
Model
Full-load amps at 460 volts
hp
kW
9 kW heater
12 kW heater
18 kW heater
24 kW heater
0.75 hp
0.56 kW
12.7 amps
16.5 amps
24.0 amps
31.6 amps
1.00 hp
0.75 kW
13.1 amps
16.9 amps
24.4 amps
32.0 amps
2.00 hp
1.50 kW
14.7 amps
18.5 amps
26.0 amps
33.6 amps
3.00 hp
2.24 kW
16.1 amps
19.9 amps
27.4 amps
35.0 amps
5.00 hp
3.73 kW
18.9 amps
22.7 amps
30.2 amps
37.8 amps
7.50 hp
5.60 kW
22.3 amps
26.1 amps
33.6 amps
41.2 amps
To Process
From Process
Process Fill
Cooling Water Supply
(optional)
Cooling Water Drain
(optional)