Westermo RM-505U-K User Manual
Page 47
man_505U-K_1.4.doc
Dec 2008
ELPRO Technologies Pty Ltd 2008
Page 47
RS232 Port
DB9 female DCE
9600 baud, no parity, 8 data bits,
1 stop bit
Inputs
Digital/Pulse Inputs
2 inputs
Suitable for voltage free contacts,
NPN transistor or TTL signal
Pulse Inputs
Transmitted as 2 x 16 bit
counters, plus pulse rate
value
Share digital inputs. Max rate
300Hz for contact or transisitor
inputs, 10KHz for TTL inputs
(50KHz on PI2 using divider)
PI2 has a configurable 1-255
integer divider
Max value for pulse rate is
1KHz.
Analogue Input
One 0 - 24 mA, 0 - 10 V
Range user-configurable
“floating”
differential
input,
common mode voltage 24V.
24V DC for powering external
loops provided, 50 mA max.
Resolution 12 bit, Accuracy <
0.1%. Transducer warm-up time
configurable 1 - 100 seconds.
Analogue Input Setpoint
Configurable high & low setpoint
may be transmitted to remote
units,
allowing
set/reset
of
remote digital outputs
System Parameters
Network Configurations
Max. number of 505K
inputs is >20 000 if
105U-C
modules
are
used as receivers.
505K is compatible with 105U
radio telemetry units which may
be used as repeaters, provision of
outputs, or as network master
unit to connect to PLC or PC
User Configuration
Configuration Software
Diagnostics
On board diagnostics
Automatic
check
on
startup
Microprocessor operation OK
Diagnostics
included
in
configuration software
Input status, test transmission
signal