beautypg.com

Westermo RM-505U-K User Manual

Page 17

background image

man_505U-K_1.4.doc

Dec 2008

ELPRO Technologies Pty Ltd 2008

Page 17

=

32

Total messages for digital input

=

4 + 364 + 32

=

400

Pulse input

Update time

1 day

Sensitivity 50

Average pulse rate is 1 pulse per hour, with peak rate of 20 per hour, for 10 hours, three times per year.

No. of change messages (normal rate)

=

0 (time for 50 pulses is more than the update time)

No. of change messages (peak rate) =

3 (three per year) * 200 (20 per hr for 10 hrs) / 50

=

12

No. of update messages per year

=

363 (approx)

Total messages for pulse input

=

12 + 363

=

375

Analogue input Sample time 1 hour

Warm-up time 5 secs

Sensitivity

3%

Update time 1 day

Average changes of >3% is twice per day

No. of change messages per year

=

2 (twice per day) * 365

=

730

No. of update messages per year

=

0 (always be a change message each 1 day)

Total messages for analogue input

=

730

Total input messages per year

=

400 + 375 + 730 =

1505

Power consumed in transmissions =

0.005 * 1505 * 2 (2 transmissions per message)

=

15 mAHr per year

Power for analogue loop supply (assume average loop current is 12mA)

No. of analogue measurements per year

=

365 days * 24 hours * 1(sample time)

=

8,760

Power for analogue loop supply

=

0.012 (from above table) * 5 (warm-up time) * 8,760

=

526 mAHr per year

Power for pulse input

Average pulse rate is 1 pulse per hour (0.0003Hz), so power required = 0.06 x 0.0003 per day

=

zero

Quiescent power

Power for quiescent current

=

3.4 per day * 365

=

1241 mAHr per year

Total power consumption per year =

15 + 526 + 0 + 1241

=

1782 mAHr

Expected battery life is

=

1700/1782

= 0.95 year

Note that battery life is shortened during configuration or diagnostics. When the serial cable
is connected to the 505K, the module does not revert to sleep mode and the power