beautypg.com

Vav system, Description, Mounting – WattMaster MG331-21-VAVCAV User Manual

Page 24: Inputs: outputs

background image

Form: WMS-OE310-21-GPC-17Controller-01A.doc

Page

1 of 1

VAV System

Description

The GPC-17 Controller is used for con-
trolling equipment or processes that can-
not be controlled using standard HVAC
Unit controllers. The WattMaster Prism
computer front end software is used to
interface with the GPC-17 controller func-
tions. The GPC-17 is designed with 6 uni-
versal inputs, 7 binary outputs and 2
analog output. Each input can be config-
ured for use with a Type III-10k ohm
thermistor temperature sensor, 4-20ma
sensor, 0-5 VDC sensor or a N.O. or N.C.
binary contact closure. Sensor reading
values can be selected for the specific
input type, such as, %RH, Deg. F, RPM,
etc.. If a thermistor type temperature sen-
sor is used, a calibration option is avail-
able to offset the actual temperature in
relation to the displayed reading. It also
has one input configures for Duct Static
Pressure and one configured for Building
Pressure. The 7 binary outputs may be
configured to operate based on any of the
8 sensor inputs, outdoor air temperature,
the GPC-17 controller’s internal schedule
or an external schedule. They can also be
configured to use AND/OR logic state-
ments. A Relay Expansion Board can be
connected to the GPC-17 to give it an
extra 8 relay outputs. In addition to the
relay outputs the GPC-17 contains two 0-
10VDC analog outputs which can be configured for simple floating point or PID control. The analog output can
also be configured to operate based on any of the 8 sensor inputs, outdoor air temperature, the GPC-17 control-
ler’s internal schedule or an external schedule. In addition an Analog Output Expansion Board can be connected
to the GPC-17, giving it two additional analog outputs.

Mounting

The GPC-17 is provided with an integral backplate for mounting inside of a control enclosure. It is recommended
that the GPC-17 be mounted in the HVAC unit control enclosure, or in a control enclosure in the building equip-
ment room. An optional factory control enclosure for the GPC-17 is available.

OE310-21-GPC

GPC-17 Controller

Technical Data

OE310-21-GPC

GPC-17 Controller

Power

24 Volt AC

Weight

1.5 lb.

Power Consumption

10 VA Maximum

Network Connection

RS-485

Operating Temp

10

°

F to 149

°

F

Protocol

HSI Open Protocol Token Passing

Operating Humidity

90% RH Non-Condensing

Communications

RS-485 - 9600 Baud

Inputs:

Outputs:

Types Allowed

Type III-10kohm sensors

Relay Qty.

7

4-20ma sensors

Relay Power Rating

(2 Amp @ 24 VAC)

N.O. Binary Contact

Analog Output Qty.

2

N.C. Binary Contact

Analog Output Signal

0-10 VDC

Total Inputs Available

8

Three Year Warranty

WattMaster reserves the right to change specifications without notice

EPROM

RAM

PAL

PIN 1

PIN 1

PIN 1

PIN 1

CPU

+V
+V

1

3
4
5
6
7
8

G
G

2

ANALOG

INPUTS

GND

SIG

+5V

ANALOG

OUTPUTS

A1
A2

G

9.00

8.25

7.63

7.13

1.00

This manual is related to the following products: