beautypg.com

Vav system, Description, Mounting – WattMaster MG331-21-VAVCAV User Manual

Page 10: Page, 1 of 1

background image

Form: WMS-StandardRoomSensor-1B.doc

Page

1 of 1

VAV System

Description

The patented design, OE21x series Standard
Room Sensor provides accurate sensing of
the room temperature. Its design allows for
flush wall mounting yet rejects the influence of
surface and internal wall temperatures. The
Standard Room Sensor is used in conjunction
with the WMVAV and the VAVBOX controllers.
Wire terminals are provided on the sensor for
connection to the controllers.

The Room Sensor’s attractive styling and off
white casing color make it suitable for most
building decors. If interior decoration requires,
the Room Sensor casing can also be painted
or wall papered without affecting the sensor's
performance. Room Sensors are available in 4
different configurations:

OE210 Sensor Plain

OE211 Sensor with Override

OE212 Sensor with Setpoint
Adjustment

OE213 Sensor with Setpoint
Adjustment and Override

Modular cable from the WMVAV or VAVBOX
controllers to the Modular Room Sensor
should not be run in conduit with other AC line
voltage wiring, or with any conductors carrying
highly inductive loads.

Mounting

The Room Sensors are designed to be
mounted on a vertical, 2” x 4” electrical box
recessed in the wall. If the wall cannot be
penetrated, a plastic surface mount box such
as those made by Wiremold

, may be used to

mount the sensor to the wall surface.

OE210, 211, 212 & 213

Standard Room Sensors

Technical Data

OE210, OE211, OE212, OE213 Standard Room Sensor

Sensor Element

Type III Thermistor
10k ohm @ 77º F

Mounting

Designed to be Flush Mounted to Wall
using Vertical 2” x 4” Handy Box (by others)

Accuracy

±

0.4º F between 40º F to 95º F

Line Loss

0.25º F max. error, using 22 AWG wire at 1000 ft

Range

-30º F to 150º F

Weight

4 oz.

3 Year Warranty

WattMaster reserves the right to change specifications without notice

OE210

OE211

OE212

OE213

Room Sensor - Plain

Room Sensor
With Override

Room Sensor

With Setpoint Adjust

Room Sensor

With Setpoint Adjust

& Overide

O

O

A

A

O

O

R

R

L

L

M

M

E

E

E

E

C

C

W

W

R

R

R

R

OVR

OVR

0.25“

TMP

GND

AUX
OUT

2.75“

2.00“

Wall Cut-Out Dimensions
When Sensor Is To Be
Mounted Without
Handy Box (By Others)

2.75“

3.25“

4.50“

2.50"

0.88“

O

A

O

R

L

M

E

E

C

W

R

R

This manual is related to the following products: