51
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
LEROY-SOMER
3776 en - 07.2007 / h
en
VMA
terminal
33/34
VMA
terminal
31/32
Designation
Function
Characteristics
6
6
ADIO3
Analogue or logic input or analogue
output 3
Assignment in standard
configuration: Analogue output
(LED control option for VMA 31 up
to 34)
Characteristics
Analogue voltage (common mode) or uni-directional
Voltage input
Full scale voltage
10 V ± 2%
Input impedance
95 k
Ω
Current input
Current range
0 to 20 mA ± 5%
Input impedance
500
Ω
Resolution
10 bits
Sampling
6 ms
Logic input (if connected to the +24V)
Thresholds
"0": < 5 V – "1": > 10 V
Voltage range
0 to +24 V
Load
95 k
Ω
Input threshold
7.5 V
Voltage output
Voltage range
0 to 10 V
Load resistor
2 k
Ω
Protection
Short-circuit (40 mA max)
Current output
(VMA 33/34 only)
Current range
0 to 20 mA
Maximum voltage
10 V
Load resistor
500
Ω
7
7
DIO1
Digital input or output 1
Assignment in standard
configuration:
External fault management
Characteristics
Digital input or output 1
Thresholds
"0": < 5 V – "1": > 10 V
Voltage range
0 to +24 V
Sampling/refreshment
2 ms
Digital input
Absolute maximum voltage
0 to +35 V
Load
15 k
Ω
Input threshold
7.5 V
Logic output
Maximum output current
50 mA
Overload current
50 mA
8
5
24V
+24V internal source
Output current
10 mA in total
Overload current
VMA 33/34: 150 mA - VMA 31/32: 50 mA
11
11
Accuracy
± 5%
Protection
Current limiting and setting to fault mode
9
8
DI2
Logic input 2
Assignment in standard
configuration: Run forward
Characteristics
Logic input (positive logic)
Thresholds
"0": < 5 V – "1": > 10 V
Voltage range
0 to +24 V
10
9
DI3
Logic input 3
Assignment in standard
configuration: Run reverse
Sampling/refreshment
2 ms
Absolute maximum voltage
range
0 to +35 V
12
10
DI4
Logic input 4
Assignment in standard
configuration: Selection of ADI1
Load
15 k
Ω
Input threshold
7.5 V
13
NA
SDI1
+24V dedicated to the safety input
Characteristics
Logic input (positive logic)
Thresholds
"0": < 5 V – "1": > 18 V
14
12
SDI2/ENA
Safety/unlocking input
Voltage range
9 to +33 V
Impedance
820
Ω
15
13
COM/RL1
Fault relay output
Characteristics
VMA 33/34: NO_NC single-pole changeover contact
VMA 31/32: NO single-pole contact
16
NA
RL1C
250 VAC maximum contact
current
- 4 A, resistive load
17
14
RL1O/RL2
- 2 A, inductive load
18
NA
SDO1
Safety contact
Characteristics
NO single-pole changeover contact
19
NA
SDO2
250 VAC maximum contact
current
- 4 A, resistive load
- 2 A, inductive load