beautypg.com

Los seconds, Ais seconds, Ext alarm – Verilink 1061 T1 Multicast (34-00268) Product Manual User Manual

Page 11: Reset timer, Nms address, Nms port rate, Supv port rate, Duplex select, Serial number, Serial number -3

background image

Configuration 3-3

1061 Multicast Card

This field displays the current status (or mode) of Side A.
Options are Active, Forced (set through the software),
Switched (set from the front panel), and Standby.

Side B Status

This field displays the current status (or mode) of Side A.
Options are Active, Forced (set through the software),
Switched (set from the front panel), and Standby.

Input Feed Mode

This field allows you to set the T1 input mode for the unit.

Normal - Input is received on a specified side. If that side
goes into alarm, the unit switches to backup side and
remains on this side until told to return to the specified side
or the current side go into an alarm state.

Primary A - Input is received on Side A and switches to
Side B only when Side A is in alarm. When Side A is
cleared, input is once again switched to Side A.

Primary B - Input is received on Side B and switches to
Side A only when Side B is in alarm. When Side B is
cleared, input is once again switched to Side B.

Force A - Input is received on Side A only.

Force B - input is received on Side B only.

Duplex Select

Duplex select allows you to select the channel (1-12) that is
full duplexed to the selected (A or B) input channel. No
channel is selected on zero. Table 3-D displays the switch
settings. The expansion settings (A EXPD, B EXPD, and A/
B EXPD) full duplex back to their respective T1 input lines.
For example, the A EXPD setting full duplexes the return
feed back to the T1 A input line; the B EXPD setting full
duplexes the return feed back to the T1 B input line; and the
A/B EXPD setting full duplexes the return feed back to the
respective T1 A and T1 B input lines.

When you bypass from an input line to
an expansion line, you must have

another 1061 unit connected to the expand
line. Failure to have a connection will cause
the signal to be interrupted.

LOS Seconds

A one second period in which the T1 received signal is
interrupted. The default threshold for alarm is five.

AIS Seconds

One second period when all ones are received. The default
threshold for alarm is five.

Ext Alarm

This field allows you to specify if the external alarm inputs
should be monitored. Options are Off and On.

Reset Timer

This field allows you to set the amount of time it takes for
the unit to clear an alarm. The default is 30.

NMS Address

This 8-pin switch (S1) sets the NMS address of the unit.
Valid addresses are 1 through 252. Address values 253
through 255 are reserved.

NMS Port Rate

This field displays the current NMS port bit rate setting (S2-
1 and S2-2). Displayed values can be 1.2, 2.4, 9.6, and 19.2
kbps. Refer to the section NMS Bit Rate on page 3-1 for
setting information.

Supv Port Rate

This field displays the current supervisory port bit rate set-
ting (S2-3 and S2-4). Displayed values can be 1.2, 2.4, 9.6,
and 19.2 kbps. Refer to the section SUPV Bit Rate on page
3-1
for setting information.

Duplex Select

This field displays the current duplex select from the T1
input (S2-5 through S2-8). Refer to the section Duplex Select
on page 3-1 o
r on page page 3-3 for setting information.

Serial Number

This field displays the serial number specific to each indi-
vidual unit.