3 remote reset input wiring – Tecfluid MX4 For FLOMID Series User Manual
Page 18

18
Terminal
Description
Relay
6
Normally
Open
Relay
1
5
Common
Relay
1
4
Normally
Open
Relay
2
3
Common
Relay
2
The relay outputs provide relays with potential free contacts (see characteristics in page 
50). 
The status of the relay contacts corresponds to the relay at rest
.
The relay contacts are not protected in any way, and therefore they must be installed 
externally 
as required in the application
, taking into account the limitations of the
characteristics of such contacts. In the case of having inductive loads, and to extend the 
working life of the relay contacts, it is recommended to use overvoltage protection (VDR 
for AC and diodes for DC loads). In all cases a fuse or some kind of protection against 
short circuits, 
should always be provided
according to the needs of the intended load.
INSTALLATION OF THE ELECTRONIC CONVERTER
2.2.3
Remote reset input wiring
2