35. OVER CURRENT CONTINUOUS
Write Command: 35
Read Command: 4d
Interpret:
1 is continuous retry when over current detected.
0 allows the RESTART ATTEMPTS value to be used.
36. OVER CURRENT RESTART ATTEMPTS
Write Command: 0f
Read Command: 5f
Interpret:
Range of value 0 to 30000
10
This is the amount of times the controller will attempt to restart the output after an
over current condition is detected.
37. JP3 DISPLAY ENABLE
Write Command: 36
Read Command: 4e
Interpret:
1 display function enabled.
0 display function disabled.