Probe adjustment, Baud rate compatibility requirements, In-e-hyclip di-v1_10 – Digi HygroClip DI digital interface User Manual
Page 17: 5 probe adjustment

IN-E-HyClip DI-V1_10
Rotronic AG
Bassersdorf, Switzerland
Document code
Unit
Instruction Manual
Document Type
HygroClip DI digital interface: instruction
manual
Document title
Page 17 of 24
© 2007; Rotronic AG
IN-E-HyClip DI-V1_10.doc
7.5 Probe
adjustment
Please consult the HW4 on-line instruction manual.
8.
Baud rate compatibility requirements
Depending on the model, devices from ROTRONIC use one of the following Baud rates as the
factory default:
• 57600 bps: HygroLog NT data logger and docking stations
• 19200 bps: HygroPalm and HygroLab indicators, HygroFlex and M33 transmitters,
HygroClip Alarm programmable alarm card, HygroClip DI interface, HygroStat MB Thermo-
Hygrostat
IMPORTANT:
• All devices connected to a RS-485 multi-drop network (master and slaves) must use the
same Baud rate
• In the case of a device with an Ethernet (TCP/IP) module, the Baud rate of the module
must be the same as the Baud rate of the device
Devices and internal Ethernet modules with mismatched Baud rate will not communicate
together.
• The Baud rate configuration of a ROTRONIC device can be changed with the Device
Manager function (Digital Interface tab) available from within the HW4 software.
• The Baud rate of a Digi Module can be changed only from the module web interface. See
separate document IN-E-TCPIP-Conf_10.doc (also available in PDF format).