Probe adjustment, Baud rate compatibility requirements, In-e-hyclip di-v1_10 – Digi HygroClip DI digital interface User Manual

Page 17: 5 probe adjustment

background image

IN-E-HyClip DI-V1_10

Rotronic AG
Bassersdorf, Switzerland

Document code

Unit

Instruction Manual

Document Type

HygroClip DI digital interface: instruction
manual

Document title

Page 17 of 24

© 2007; Rotronic AG

IN-E-HyClip DI-V1_10.doc

7.5 Probe

adjustment

Please consult the HW4 on-line instruction manual.

8.

Baud rate compatibility requirements

Depending on the model, devices from ROTRONIC use one of the following Baud rates as the
factory default:

• 57600 bps: HygroLog NT data logger and docking stations

• 19200 bps: HygroPalm and HygroLab indicators, HygroFlex and M33 transmitters,

HygroClip Alarm programmable alarm card, HygroClip DI interface, HygroStat MB Thermo-
Hygrostat


IMPORTANT:

• All devices connected to a RS-485 multi-drop network (master and slaves) must use the

same Baud rate

• In the case of a device with an Ethernet (TCP/IP) module, the Baud rate of the module

must be the same as the Baud rate of the device


Devices and internal Ethernet modules with mismatched Baud rate will not communicate
together.

• The Baud rate configuration of a ROTRONIC device can be changed with the Device

Manager function (Digital Interface tab) available from within the HW4 software.

• The Baud rate of a Digi Module can be changed only from the module web interface. See

separate document IN-E-TCPIP-Conf_10.doc (also available in PDF format).