beautypg.com

Super Systems Compact HMI User Manual

Page 15

background image

Compact HMI and Compact HMI Editor Operations Manual

Super Systems Inc.

Page 15 of 60

For ModbusRTU Connections

(Example: Figure 13)

• Host Address: The address of the

touch screen. Normally, this setting

can be kept as the default.

• Target Address: The address of the

data device. Normally, this setting can

be kept as the default.

• COM Port: The COM (serial) Port with

which the Compact HMI touch screen

will be connected to the data device.

This must match the actual COM Port

on which the serial cable is connected

to the touch screen.

The default COM Port is COM 2. Some

touch screens may have only one COM

Port. In such a case, COM 1 will need

to be used for the data device

connection, and an Ethernet

connection will need to be used for the

SSi 9000 Series controller.

• Read Offset: The register address

where Compact HMI starts reading.

This must be defined to the word level

within the data device.

Figure 13 – New Connection window (ModbusRTU)

• Read Count: The default number of registers,

starting with the Read Offset, that will be read.

The default is 100. This value must not exceed

the number of registers actually defined within

the data device.

• Baud Rate: The rate (in units per second) at

which communications bits are sent between

the touch screen and data device. The default is

19200.

Generate Tags checkbox: When checked, this

checkbox will cause tags to be generated. The tags

generated will be based on the Read Offset and

Read Count defined in this menu. For example, if

the Read Offset is 0 and the Read Count is 100, the

tags generated will be named Tag0, Tag1, and so

on, through Tag99.

For ModbusTCP Connections

(Example: Figure 14)

• IP Address: The IP address of the data

device.

• Port: The port number on the data

device through which the data device

will exchange data.

• Read Offset: The register address

where Compact HMI starts reading.

This must be defined to the word level

within the data device.

• Read Count: The default number of

registers, starting with the Read

Offset, that will be read. The default is

100. This value must not exceed the

number of registers actually defined

within the data device.

Figure 14 – New Communications Window (ModbusTCP)


• Generate Tags checkbox: When checked, this

checkbox will cause tags to be generated. The

tags generated will be based on the Read

Offset and Read Count defined in this menu.

For example, if the Read Offset is 0 and the

Read Count is 100, the tags generated will be

named Tag0, Tag1, and so on, through Tag99.