ERT1557

Operating Instructions

- 15 -

5.4.4 Press and release the TEST key. The measured

resistance will appear on the LCD after a few

seconds. To save the result, refer to section 6.2.

5.5 RA 4 Pole


5.5.1 Rotate the rotary switch until the R

A

4pole

test is

selected.


5.5.2 Connect the Es, E, H and S test leads to the test

spikes.

5.5.3 Insert the test spikes into the ground in the order

E, Es, S and H. Ensure the spikes are equi-

spaced.


5.5.4 Input the appropriate distance between the test

spikes into the ERT1557 by pressing the F3
(Distance) function key. Press F1 (

D) or F2 (Ñ)

function keys to either increment or decrement

the distance, in metres.


5.5.5 To perform the soil resistivity test press and

release the TEST function key.

5.5.6 The measured soil resistivity will appear on the

LCD after a few seconds. To save the result,
refer to section 6.2

ERT 1557

E

ES

S

H

Potential

Electrode

Current

Electrode

Figure 5