Component Diagnostics

Membrane Switch

Unplug and check connector pins (left side is pin
1), read about 10 ohms when activating the button,
and OL when not pressing the button: Pin 2-3
On/Off Switch; 4-3 Clean Reset Switch

Compressor

Check temperature of compressor, if very hot, add
access valves to refrigeration system and check
system pressures. If very low, add very small
amount of R-134a. If pressure does not improve,
capillary tube may be restricted. If pressures
improve find and correct refrigerant leak.

If compressor temperature is normal and
compressor is drawing high amps, check start
relay.

If relay is good and compressor is not overheating
but drawing high amps, replace compressor.

Pump Switch - Pump model only

The pump switch activates the pump based on
pressure to it from water inside the drain hose to
the pump inlet. It is normally open. When pressure
increases the switch closes, turning on the pump
motor until the pressure falls.

The safety switch (the red one) is normally closed
and operates at a higher activation pressure than
the pump switch. It stops operation of the machine
if it opens.

Ice Level Sensor

To operate, the unit must have:

Power to the controller

Water sensed

Call for ice

With power on and Ice Making light on, check
sensor connector, if secure and the unit not
operating, remove connector and jump the two
middle pins at J9 on the controller together. Unit
should start. If it does, replace the sensor, if not,
replace the controller.

May 2011

Page 11

SCN60
Service

Comp

Auger