OPERATION:

Beginning at the compressor, the refrigerant
502 is compressed into a high temperature
gas. The discharge line directs this gas to the
condenser and to the head pressure control
At the remote condenser the gas is cooled
by air and it then condenses into a liquid. This
high pressure liquid then goes through the
liquid line to the liquid line connection at the
head pressure control. If the head pressure
is high enought the liquid refrigerant will go
through the valve and enter the receiver.
From the receiver, the liquid refrigerant flows
through the liquid line valve and then to the
expansion valve.

The thermostatic expansion valve meters
liquid refrigerant into the evaporator, the
volume of liquid refrigerant depending upon
the temperature of the evaporator; warmer
evaporators get more refrigerant and colder
evaporators get less. At the evaporator, the
refrigerant enters an area of relatively low
pressure, where it can easily "boil off" or
evaporate. As it evaporates, it absorbs heat
from the evaporator and whatever is in contact
with it (such as the water inside it). After the
evaporator, the refrigerant, now a low
pressure vapor, goes through the suction line
back to compressor, where the cycle is
repeated.

REMOTE CONDENSER

DETAIL OF HEAD

PRESSURE CONTROL

VALVE

LIQUID LINE

VALVE

THERMOSTATIC

EXPANSION

VALVE

EVAPORATOR

COMPRESSOR

HIGH PRESSURE

CONTROL SWITCH

RECEIVER

HEAD

PRESSURE

CONTROL

VALVE

DISCHARGE

LINE

LIQUID LINE

NM1250R

November, 1988