Refrigeration System Operation

The FDE474 uses a forced draft condenser,

capillary tube and hermetic compressor. The

system uses R-134a as a refrigerant. High

pressure, high temperature refrigerant is forced

thru the condenser where it discharges enough

heat to condense. The high pressure liquid

refrigerant then passes thru the capillary tube

which causes a pressure drop in the evaporator.

As the high pressure liquid refrigerant moves into

the evaporator’s area of low pressure, the warm

water and low pressure cause the refrigerant to

evaporate and absorb heat from the metal walls of

the evaporator. After the refrigerant has flowed thru

the evaporator it goes back to the compressor thru

the suction line as a low pressure vapor. At the

compressor the cycle is repeated.

The FDE474 uses a low side pressure control as a

safety, it will shut the system down if the suction

pressure is too low for reliable operation.

System Characteristics:

·

Typical Low Side Pressure:

13 - 14 PSIG

·

Typical Discharge Side Pressure:

135 - 175 PSIG

·

System Refrigerant Charge:

14 ounces of R-134a

FDE474

March 2000

Page 13

Capillary Tube

Dryer

Air Cooled

Condenser

Compressor

Evaporator

Refrigeration System Schematic