7. Install and configure the sensor.
8. Install the cover and snap into place.
VOLTS
OUTPUT SELECT
mA
RH OUT
10V 5V
10V 5V
50/95 32/122
C
F
T OUT
T RANGE
T SCALE
WARNING: Output select must be
correct before applying power.
RH
SENSOR
TEMP
SENSOR
VOLTS
OUTPUT SELECT
mA
RH OUT
10v
5v
10v 5v
50/95
32/122
ºC
ºF
T OUT
T RANGE
T SCALE
6. Wire the backplate.
POWER SOURCE
15 to 30VDC or 24 VAC
DIGITAL CONTROL
RH Return
Temp Return
Thermistor/RTD Override
Setpoint Slider
-
--
+
RTD/Thermistor
RTD/Thermistor
Temp Transmitter OUT (4-20mA RTN)
Slider Right
Slider Wiper
Slider Left
RH OUT (4-20mA RTN)
POWER SOURCE
15 to 30VDC or 24 VAC
DIGITAL CONTROL
RH IN (0-10V)
Temp IN (0-10V)
Thermistor/RTD Override
Setpoint Slider
-
--
+
GND
RTD/Thermistor
RTD/Thermistor
Temp OUT
Slider Right
Slider Wiper
Slider Left
RH OUT
Current Output (2 wire, 4-20mA)
Voltage Output (3 wire, 0-10V)
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a mini-
mum of two for secure mounting.