RLE GD200 User Manual
Option accessories
D
C
B
A
A
B
C
D
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
Quatrosense Environmental Ltd. ANY
REPRODUCTION IN PART OR AS A WHOLE
WITHOUT THE WRITTEN PERMISSION OF
Quatrosense Environmental Ltd. IS
PROHIBITED.
PROPRIETARY AND CONFIDENTIAL
NEXT ASSY
USED ON
APPLICATION
DIMENSIONS ARE IN INCHES
TOLERANCES:
FRACTIONAL 1/32
ANGULAR:
MACH .5 degrees BEND
TWO PLACE DECIMAL .02
THREE PLACE DECIMAL .010
INTERPRET GEOMETRIC
TOLERANCING PER:
MATERIAL
FINISH
DRAWN
CHECKED
ENG APPR.
MFG APPR.
Q.A.
COMMENTS:
DATE
NAME
Quatrosense Environmental Ltd
TITLE:
SIZE
B
DWG. NO.
REV
WEIGHT:
SCALE: 1:8
UNLESS OTHERWISE SPECIFIED:
B
XY
XY
XY
2010/02/25
2010/02/25
2010/02/25
Q5
INSTALLATION DRAWING
SHEET 1 OF 5
85950-002-000
DO NOT SCALE DRAWING
SPECIFICATION
INPUT POWER:
+24VDC nominal, range: 18 to 30VDC 0.3A DC Total Max.
~24VAC nominal, range: 15 to 24VAC 50/60HZ 0.3A AC Total Max.
(AC must not be grounded)
FUSE:
F2 on Main Board: Polyswitch 750mA
Polyswitch device resets after the fault is cleared and power to the
circuit is removed
SENSOR:
Combustible gases: Catalytic
Toxic gases and Oxygen: Electrochemical
OUTPUT SIGNAL:
RS-485 with OPTIMUX PROTOCOL AND MODBUS PROTOCOL
AVAILABLE CONTROLLER: M-CONTROLLER or Q4 CONTROLLER
4-20mA Analog Output, 1-5VDC, 2-10VDC Output
3X SPDT RELAYS: 1.0A MAX. @30VDC (RESISTIVE LOAD)
0.3A MAX. @125VAC (RESISTIVE LOAD)
ENCLOSURE:
IP 66 & NEMA 4, 4X, 12 & 13
OPERATING TEMPERATURE:
-40°C to 70°C, depends on sensor specification
AMBIENT HUMIDITY:
5% TO 95% RH (NON- CONDENSING)
STORAGE TEMPERATURE:
0°C to 20°C, depends on sensor specification
SIZE:
150mm X 90mm X 65mm
WEIGHT:
LESS THAN 0.5lbs
Option Accessories:
Pump-thru & Cal Cap Kit
SKU#: 85930-006-000
Splash Guard Kit
SKU#: 85930-007-000
Duct Mount Adapter
Kit: 85930-040-000
Q-View & USB-RS485 Converter Kit: 85930-004-000
*Option Accessories are not included in Q5 Standard Package.
REVISIONS
ECN
REV.
DESCRIPTION
DATE
DRAW
CHECK APPROVED
924
A
Initial Release
2010/02/25
XY
XY
XY
929
B
Update Duct Mount Kit
2010/08/23
XY
XY
XY