RLE T120D User Manual

T series, Notice, Temperature transmitters

background image

VERIS INDUSTRIES

environmental SenSorS

inStallation GUiDe

Z201986-0N

PAGE 1

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

04101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Temperature Transmitters

Installer’s Specifications

Input Power

4-20mA version - Loop powered 12-30VDC only, 30mA max;

0-5/0-10V versions - 12-30VDC/24VAC, 15mA max

Temp Output

2-wire, loop powered 4-20mA or 3-wire, 0-5V/0-10VDC

(switch selectable in TWxA)

Sensor Type

Solid-state, integrated circuit (Transmitter)

Accuracy

±0.5°C (±1°F) typical

Ranges

0° to 50°C (32° to 122°F), -40° to 50°C (-40° to 122°F)

Wiring (TOA and TDDA)

22AWG; 2-wire: 4-20mA;

3-wire: Voltage output models

T SerieS

T SerieS

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

Product IdentIfIcatIon

quIck Install

TDDA

Drill a hole in the duct.

1.

Insert the temperature probe, until the junction box is flat against the outer

2.

surface of the duct.

Use screws to secure the junction box to the duct.

3.

Wire as shown (see Wiring section).

4.

TOA

Locate sensor in an outside area, out of direct sunlight (e.g. under an eave, north

1.

side of building).

Mount the housing.

2.

Wire as shown (see Wiring section).

3.

TWxA and TW

Mount the housing vertically on an interior wall in the area to be monitored, in

1.

a location where air circulates freely. Locate unit away from air outlets, corners,
exterior walls, windows, and doors.

Wire as shown (see Wiring section).

2.

TDDA

TOA

TWxA/TW

TDDA

Output

M = 4-20mA
V = 0-5/10VDC

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Range

1 = -40° to 50° C
(-40° to 122°F)
2 = 0° to 50°C
(32° to 122°F)

TOA

Cal Certificate

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Range

1 = -40 to 50°C
(-40° to 122°F)
2 = 0° to 50°C
(32° to 122°F)

Output

M = 4-20mA
V = 0-5/10VDC

Sensor Type

TW

A

Local Display

= Transmitter
selectable
outputs

L = LCD
X = No

Setpoint/Override

Cal Certificate

0 = None
2 = 1k Setpoint
3 = 10k Setpoint
4 = 1k Setpoint with override
5 = 10k Setpoint with override

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Sensor Type

TW

Local Display

L = LCD
X = No

Setpoint/Override

Cal Certificate

0 = None
2 = 1k Setpoint
3 = 10k Setpoint
4 = 1k Setpoint with override
5 = 10k Setpoint with override

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor

K = 10k w/11k shunt,Thermistor
M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
P = 10mV/°C, Linitemp
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor