General Installation Instructions

While the instructions to mount each spot detector to the floor are the

same, each model of SD connects differently with its controller. Follow these

instructions to mount your spot detector to the floor; then continue to the

directions specific for your SD.

1. Determine the spot detector’s location

2. The angle of the sense probes can be adjusted to change the sensitivity of

the SD. The closer the probes are to the floor, the smaller the quantity of

water required to trigger the sensor. Adjust the sense probes to the desired

height. Be sure the probes don’t touch each other.

3. Ram set 6/32 threaded studs in the floor on 2.5” centers or apply mastic.

4. Place the spot detector over the studs or mastic and secure.

From this point, each spot detector’s installation varies a bit. Refer to the

instructions for your particular unit.

SD

The SD is designed to primarily function with RLE controllers, specifically the

FMS, F-series, RA1x2, or the LDRA6. The SD functions like a switch - the circuit

remains open until a leak is detected. The sense probes detect a leak, which

causes the circuit to close, which then triggers an alarm. If the SD is operating

on 12-36VAC power, the circuit will reset and open automatically once the leak is

no longer present. If the SD is operating on 18-36VDC power, the circuit must

be manually reset after the leak is cleared. To do this, you must break power

to the device, which will reset the circuit. Even if the water leak is no longer

present, power must be broken to manually reset the DC-powered SD.

The SD comes with a two-wire open lead that allows it to be wired directly to

the controller’s terminal block. Connect the white/red and black leads to the

appropriate terminal blocks on the controller.

This sensor will alarm with a small

quantity of water present.

This sensor requires a larger amount of

water to be present before it alarms.

Falcon

SD

Spot Detector Quick Start Guide

designed for use with SD, SD-Z1, SD-Z, and SD-RO1 products

Thank you for purchasing a SeaHawk spot detector. This guide describes how to

install all models of spot detectors available from RLE Technologies.

If you need further assistance, please contact RLE Technologies via our website -

http://www.rletech.com/support or call us at 800.518.1519, Option 2.

SD-Z1

The SD-Z1 is a single zone spot detector, designed for zone leak detection

systems including the LD300, LD1000, and LDRA6. RLE recommends using only

one SD-Z1 per zone.

The SD-Z1 comes with a four-wire open lead that allows it to be wired directly to

the controller’s designated terminal block. Connect the four wires - red, green,

black, and white - on the SD-Z1 to the terminal block on the controller.

SD-Z1

Sense

Probes