Afs(wm/dm), Afs-(wm/dm) f200 integration, Fms sensor wiring guide – RLE FMS User Manual
Page 8: Figure 8.1: fms wiring, Fms configuration

SHEET:
8 OF 16
104 Racquette Drive
Fort Collins, CO 80524
(970) 484-6510 Phone
(970) 484-6650 Fax
www.rletech.com
FMS Sensor Wiring Guide
10061_FMS Rev 2.0 (8/13)
AFS-(WM/DM) F200 Integration
FMS Configuration
Figure 8.1: FMS Wiring
1 2 3
SW1
SW2
SW3
FMS AFS-xx Input Configuration Interface
1
2
3
4
P1
V DC
TB 1
V DC
+ -
EXT ERNAL
24VDC
+ +
Ch1
+ -
Ch2
+ -
Ch3
+ -
Ch4
+ -
TB 2 Input 1-4
Ch5
+ -
Ch6
+ -
Ch7
+ -
TB 3 Input 5-8
Ch8
+ -
EXT ERNAL
GND
- -
TB 4
NC NO C
RELAY 1
NC NO C
RELAY 2
1. Set Jumper Switches on AFS-XX to appropriate
settings.
Output Selection SW1:
4-20mA Output
Working Range SW2:
0-2000 Ft/Min Range
0-3000 Ft/Min Range
0-4000 Ft/Min Range
Response Time SW3:
Fast
Slow
2. Set FMS Input Channel to an Analog 4-20 mA.
3. For a 0-2000 Ft/Min Range, use a gain of 500 and an
offset of -500.
4. For other settings, use the integrated gain/offset
calculator.