Remko fbr-2, Troubleshooting and customer service, Analogue remote control with room sensor – REMKO FBR-2 User Manual
Page 10
10
REMKO FBR-2
ANALOGUE REMOTE CONTROL
WITH ROOM SENSOR
Fault
Possible cause
Checks
Remedial measures
Communication
fault
Bus and sensor cables
are too close to
power cables
Check position of
connection cables
Reposition cables with suf-
ficient spacing
Polarity switched
(+/-)?
Check polarity
Connect with correct
polarity
BUS feed
too low
Check voltage on
BUS plug
A voltage of at least 8V
DC mustbe presentbe-
tween the "+" and "-"
terminals - add external
power if not.
The equipment and components are manufactured using state-of-the-art production
methods and tested several times to verify their correct function. If malfunctions
should occur, please check the functions as detailed in the list below. Please inform
your dealer if the unit is still not working correctly after all the functional checks have
been performed!
Troubleshooting and customer service