beautypg.com

Remko, Way switching valve dn32, Manual mode – REMKO DN 32 User Manual

Page 8

background image

8

REMKO

3-WAY SWITCHING VALVE DN32

Manual mode

The 3-way switching valve can be
operated manually until the time of
commissioning or in case of a defect of
the actuator. The electrical actuator must
be removed in this case.

The replacement of the actuator
must take place in a de-energised
(electrical) state. Also disconnect the
main connection to the actuator.

To do so, proceed as follows:

1. Loosen fastening screw "2" of the

actuator. This is under the black
cover. Then you can remove the
actuator.

Removal of the actuator

Removal of the actuator

2

2. The 4-way switching valve can

be moved to the desired position
using a large screwdriver. This
must be able to take place
smoothly and easily. Otherwise the
valve must be replaced, cleaned
and/or repaired.

Manual mode

ATTENTION