REMKO RKW INOX User Manual
Page 8
8
Determining the Operating Mode (Status)
The Status menu is used to determine the current operating mode of the various system components such as oper-
ating hours, outputs currently set, the current actual values of the sensor inputs and any current malfunctions.
Pressing the STATUS button takes you to the Status menu (Status LED is lit up). The left-hand value display now
indicates the current operating mode of the statuses in the right-hand code display using the index described in the
table below. These can be listed by pressing the arrow keys in sequence:
Status
Status Description
Index
Meaning
01
Compressor 1
01
02
03
04
06
Compressor 1 in cooling mode
Compressor 1 in heating mode (not in use)
Compressor 1 in defrost cycle (not in use)
Compressor 1 in time delay ON
Compressor 1 OFF
02
Run time Compressor 1
# (value in hours)
Operating hours of Compressor 1
03
Fan(s) Cycle 1
01
02
04
06
In operation
Off (defrost for heating pump)
Time delay ON
OFF
05
Rotations condenser fan(s) Cycle 1
# (value as a %)
Fan rotation as a percentage
21
Compressor 2
- - -
01
02
03
04
06
Not installed
Compressor 2 in cooling mode
Compressor 2 in heating mode (not in use)
Compressor 2 in defrost cycle (not in use)
Compressor 2 in time delay ON
Compressor 2 OFF
22
Run time Compressor 2
- - -
# (value in hours)
Not installed
Operating hours of Compressor 2
23
Fan(s) Cycle 2
- - -
01
02
04
06
Not installed
Fans in operation
Off (not in use)
Time delay ON
OFF
25
Rotations condenser fan(s) Cycle 2
- - -
%
Not installed
Fan rotation as a percentage
40
Sensor incoming water temperature
ST 1 (Cycle 1)
- - -
# (value in °C)
ON
OFF
ERR
Not installed
Actual value in 0.1°C intervals
Sensor activated
Sensor not activated
Sensor malfunction or failure
41
Remote control ON/OFF
- - -
ON
OFF
Remote control not installed
Remote control active
Remote control locked
42
Sensor outgoing water temperature
ST 2 (Cycle 1)
- - -
# (value in °C)
ON
OFF
ERR
Not installed
Actual value Cycle 1
Sensor activated
Sensor not activated
Sensor malfunction or failure
43
Sensor outgoing water temperature
ST 3 (Cycle 2)
- - -
# (value in °C)
ON
OFF
ERR
Not installed
Actual value Cycle 2
Sensor activated
Sensor not activated
Sensor malfunction or failure
44
Sensor condenser temperature
ST 5 (Cycle 1)
- - -
# (value in °C)
ERR
Not installed
Actual value
condenser
Cycle 1
Sensor malfunction or failure
45
Sensor condenser temperature
ST 6 (Cycle 2)
- - -
# (value in °C)
ERR
Not installed
Actual value condenser Cycle 2
Sensor malfunction or failure
46
Cold water pump
- - -
01
06
Not installed
Pump in operation
Pump not in operation
47
Run time cold water pump
- - -
# (value in hours)
Not installed
Operating hours of the pump
48
Defrost heating
(not in use)
- - -
01
06
Not installed
Heating in operation
Heating not in operation
8
1
STATUS
1
0
4
0
2
0
6
0
STATUS
Programming process