Troubleshooting

This unit has been designed based on state-of-the-art manufacturing methods and it has been tested repeatedly to
ensure that it is working properly. However, should problems occur, refer to the following list.

Problem

Alarm

Possible cause

Check

Remedy

The unit
does not
start or it
switches
itself off
automati-
cally.

Power failure

Are all other electrical components
working?

Check voltage and wait for the
unit to start again.

Power fuse / power supply de-
fective

Are all other electrical components
working?

Maintenance by authorised
personnel

Waiting period too short

Is the COMP LED blinking?

Schedule longer waiting periods

Regulation is not working

Is the LINE LED and to the
COOL LED lit up?

Connect current and select the
COOL operating mode

Incorrect discharge tempera-
ture or parameter setting

Check setting

Change setting

E01/E02
E21/E22

High-low pressure alarm

Are the fans rotating?
Is the pressure in the cold cycle OK?

Have checked by authorised
company

E00/E21

Remote control / Connection
to C2-DIN defective

Is the display working?
Is the connection OK?

Replace remote control or re-
establish connection between
CH-DIN and C2-DIN

E03/E23 Compressor overheating

Is the temperature of the compressor
above approx. 100 °C?

Maintain operating ranges, clean
fins

E04/E24

Liquefaction temperature too
high

Are the fins clean and have the oper-
ating ranges been maintained?

Clean fins, place unit in the
shade

E05/E25 Frost protection activated

Is the supply temperature 4°C or
lower?

Increase discharge temperature

E06/E07/
E26/E27/
E40

Sensors defective ST1 to ST6

It is the alarm activated when the
sensor is replaced?

Replace defective sensors

E41

Flow switch (differential pres-
sure monitor) activated

Are the following values OK:

Volume of current (too large/small)

No air in the monitoring pipes

Circulation pump

Does the monitor switch on and off

Stop mechanisms are open

Water pressure too high/low

Have checked by authorised
company

E42

Hardware defective

Does the regulation function
smoothly?

Have regulation replaced by
authorised company

Compressor contact defective

Is the COMP LED lit up and is there
current on the contact?

Have the contact or compressor
replaced by an authorised com-
pany

The unit is
either not
cooling at
all or only
a little bit

Heating capacity was in-
creased

Has there been a structural change? Maintain safety zones

Supply temperature too high

Is the supply temperature approx.
5 ... 10 °C?

Reduce discharge temperature

Air in the system

Have automatic ventilators been
mounted on the highest possible po-
sition?

Ventilate manually or integrate
ventilators

Liquefaction temperature too
hot

Are the fins clean and have the oper-
ating ranges been maintained?

Clean fins, place unit in the
shade, maintain operating ranges

Incorrect parameter settings

Check settings

Change settings

Sporadic operation because
cooling requirements are too
low

Has the system been designed for
smaller measurements?

Increase the quantity of water by
installing a storage module

Water
leaks out
of the unit

Leaks in pipes or defective in-
sulation

Are there leaks and have all lines

been insulated?

Seal and insulate

Incorrect electrical rotational
direction

Did the phase-sequence relay switch
through?

Change the rotational direction