17

RKW 1000 / 1600 INOX

Incoming water

Outgoing water

RKW 2600 INOX

Incoming water

Outgoing water

RKW 3600 / 4500 INOX with separate storage module

Incoming water

Outgoing water

Incoming water

Outgoing water

Hydraulic connection RKW 8000 / 9800 INOX

Incoming water

Outgoing water

Storage module for
RKW 3600 to 9800 INOX

For the RKW 3600, 4500, 8000 and 9800 INOX models,
it is not necessary to use a storage tank for certain
types of use

Other types of application absolutely require the volume
of water to be increased, for example, to extend the op-
erating time of the chiller and prevent sporadic opera-
tion.

Five storage modules have been designed to meet
these practical requirements:

1.

Storage module 1 for RKW 3600 and 4500 INOX,
216 l tank, safety component 3 kPa and MAG,
without pump,
Ref.No.: 1611530

2.

Storage module 2 for RKW 3600 and 4500 INOX,
216 l tank, safety component 3 kPa and MAG,
including prompt, V

nenn

: 6,2/7,6 m³/h, p

max

: 124/118 kPa


Ref.No.: 1611540

3.

Storage module 3 for RKW 8000 and 9800 INOX,
2 x 216 l tanks, safety component 3 kPa and MAG,
without pump,
Ref.No.: 1611545

4.

Storage module 4 for RKW 8000 and 9800 INOX,
2 x 216 l tanks, safety component 3 kPa and MAG,
including pump, V

rated

: 13,4/16,9 m³/h, p

max

: 90/82 kPa


Ref.No.: 1611550

5.

Storage module 5 for RKW 8000 and 9800 INOX,
2 x 216 l tanks, safety component 3 kPa and MAG,
incl. 2 x pumps, V

rated

: 13,4/16,9 m³/h, p

max

: 95/65 kPa

Ref.No.: 1611555

The storage modules 1 and 2 are to be attached under
the RKW 3600 and 4500 INOX chillers by means of the
standard connection line. In Module 2, the circulation
pump is installed at the factory.
The storage modules 3, 4 and 5 can be set up on top of
one another to save space. The circulation pump(s) of
Modules 4 and 5 cannot be placed inside the modules
due to the design. They must be set up separately.
The hydraulic components which are to be placed in an
easily accessible location include the insulated storage
tank, a safety component, a manometer, a membrane
expansion vessel (MAG) and a filling connection with
ball stop valve.

Hydraulic Connections

Incoming water

Outgoing water

RKW 3600 / 4500 INOX with the storage module below