Regulation

CH–DIN regulation of all RKW INOX units

The CH–DIN microprocessor regulates the chiller for all
INOX units. It is located in the electrical switch box of
the unit and monitors all control and safety functions:

Controls and displays incoming and outgoing cold
water temperatures

Displays the time delay of the compressor and fan

Checks that the outgoing water temperature is not
too low (frost monitoring)

Displays and controls all safety mechanisms that
have been stopped due to a malfunction

Displays the operating mode

Regulates the condensation temperature

The regulator consists of the basic unit to control unit
operation. A fan board is connected to the basic unit
that controls the rotation of the fan motors by regulating
the output current depending on the liquefaction tem-
perature.
Models RKW 3600 INOX and higher have two cold cy-
cles. The second cycle cannot be regulated by the CH–
DIN basic unit because there are not enough inputs and
outputs. For this reason, the extra C2-DIN regulator
controls the second cycle. Programming is, however,
still performed using the CH–DIN basic unit.

Value Display

The value display shows the target value in degrees
with one decimal place in Celsius. It can also display:

All parameter settings

The codes for all alarms

The status of the functions

The operating hours

The shut-off status

The current delays

A square LED displays minus temperatures and an LED
in the top left-hand corner shows the multiplier of the
displayed value with 100.

8

8.

8

Arrow Keys

The set value for each parameter can be changed with
the arrow keys.
When the parameter programming operating mode is
accessed (via the MENU button), both displays show a
value (continuous display). After the SET button has
been pressed, the code display (parameters) starts
blinking. The displayed values can be increased or de-
creased using the arrow keys. If the SET is pressed a
second time, the value display blinks. The new values
are saved by pressing the SET button again. Both dis-
plays switch from a blinking display to a continuous display.

MENU Button with one LED
The MENU button provides access to the parameter list
and displays the parameters on the code display and
the associated value on the value display.

MENU

CH– DIN panel

CH-DIN

Line

Alarm

Comp

Heat

Cool

STATUS

MENU

ON/OFF

RESET

8

8

8

8.

8

SET

MODE

e

Value display

Code display

Arrow keys

MODE button

SET button

MENU button

STATUS button

ON/OFF

RESET button

Code Display

The code display indicates the number of the parameter
(or the function) whose value or status appears in the
value display. If a parameter is shown in the code dis-
play, the setting appears in the value display.

8

8

STATUS Button with one LED

The STATUS button provides access to the status list
and displays the status settings by pressing the arrow
keys.
The code display shows the function number of the
function list and the value display shows the corre-
sponding setting. The codes and their descriptions are
described in the table on page 8.

STATUS

The panel has two displays: the value display (three
numbers on the left) and the code display (two numbers
on the right).

The buttons

allow operating

processes (parameters) and their associated values to
be changed.

STATUS

MENU

ON/OFF

RESET

SET

MODE

MODE Button with two LEDs

The regulation mechanism was designed for use of a
chiller in the cooling operating mode

and as a

heat pump in the cooling and heating operating
modes.
Only the summer operating mode (cooling mode)
may be used for all INOX units
.

MODE

Cool

e

Heat

Cool