Condenser

fan 1

Terminal strip M1

Terminal

strip

M2

Compressor motor 2

Input

400 V / 3 Ph ~, N, PE

50 Hz

Fan rotation regulation

board

TK 1 and TK 2

(winter regulation)

Microprocessor

regulation

Additional

module

Overheating protection condenser

Overheating protection condenser 1

Compressor motor 1

Circulation pump

Condenser

fan 2

Frequency block

Frequency block

Differential

pressure

monitor

INTERNAL

Neutral con-

tact for cooling

regulation

EXTERNAL

ST 1: Temperature

Incoming water

ST 2: Temperature

sensor outgoing water

ST 5: Temperature

sensor

HP Pressure absorber

High pressure

LP Pressure absorber

Low pressure

BUS

BUS

in

12V 12V

20 21 22 23

out

24

L1 N

L1

12V

12V

N

Pri

230V~

CH – DIN regulation /

C2 – DIN regulation

Additional module for

the remote control

Transformer 220 / 12 V~

in the switch box RKW

Operating module

Maximum line length
50 meter

Assembly Instructions

1. Place the two connection lines with a minimum

cross-section of Cu 1.5 mm² between the RKW and
the operating module (max. 50 m).

2. Connect the operating module electrically.

3. Switch the RKW so that it is neutral (i.e. no current)

and connect the 250 mm long bus-interface line to
the additional module.

4. Connect the line of the data transfer to the terminal

strips 23 and 24 (pay attention to polarity) of the ad-
ditional module and the terminal strips on the trans-
former for the current supply.

Electrical Wiring Diagram RKW 3600 INOX / 4500 INOX

Connecting the Remote Control RKW 1000 INOX to 9800 INOX

CS-DIN/TTL

TS-W

Phase-
sequence
relay