List of the alarm codes

Shutting Down the Unit

Temporary shutdown

If the unit is to be taken out of operation for a longer pe-
riod of time, for example, over the winter, proceed as
follows:

1. Use the remote control to shut down all of the inner

units.

2. Switch off the internal regulation in the chiller (or the

remote control).

3. Have the percentage of glycol is checked by an

authorised company.

4. If only water was used in the hydraulic cycle and no

brine (water and antifreeze), this water must be
drained from system components in areas suscepti-
ble to frost during the period of non-operation. When
the unit is put back into operation, the amount of wa-
ter that has been drained must be refilled!

5. Check the inner units and the chiller for any visible

damage.

6. Clean the inner units and outer parts as described in

section 5 “Maintenance” and cover the chiller, if pos-
sible, with a plastic sheet to protect it from weather
conditions.

When the unit is put back into operation after a long pe-
riod of non-operation, it must first be checked for exter-
nal damage before operation.

Code

Alarm Type

AUTO

MANUAL

E00

Remote control defective (open contact)

E01

High pressure alarm Cycle 1

E02

Low pressure alarm Cycle 1

E03

Condenser overheating Cycle 1

E04

Condenser temperature too high

E05

Frost protection Cycle 1 activated

E06

Sensor defective ST 2 outgoing water Cycle 1

E07

Sensor defective ST 5 condenser Cycle 1

E21

High pressure alarm Cycle 1

E22

Lobe pressure alarm Cycle 1

E23

Condenser overheating Cycle 2

E24

Condenser temperature too high

E25

Frost protection Cycle 2 activated

E26

Sensor defective ST 3 outgoing water Cycle 2

E27

Sensor defective ST 6 condenser Cycle 2

E40

Sensor defective ST 1 incoming water

E41

Flow switch (differential pressure monitor) activated

E42

Hardware defective

The second parameter level can be

programmed to reset the alarms.

Enter the changed resets in the left-

hand column.

All settings made at the factory

have been pre-programmed to

AUTOMATIC.

Alarm Description

To protect the unit, the CH-DIN regulation and the C2-
DIN additional regulation use sensors to check the unit’s
safety mechanisms for temperature, pressure, internal
configuration, etc.
The value display of the CH-DIN regulation indicates the
alarm code by displaying the letter E followed by two
numbers. The cause of the alarm can be determined by
finding the code in the table below. The C2-DIN addi-
tional module also displays the alarm with a correspond-
ing LED.
On the second parameter level, resetting the alarm can
be programmed after the malfunction has been fixed
The alarms are pre-programmed to automatically reset
at the factory.
If the alarms have been reprogrammed to be reset
manually, the alarm must be reset after the problem has
been fixed by switching the CH-DIN and then on again
with the ON/OFF/RESET button (see programming ex-
ample below).

Resetting the alarms after the problem has been fixed
The alarms can be reset by following the programming process below. As an example, the compressor switched off
due to a malfunction caused by dirt in the condenser fins.

3

1

2

0

Overheating of the

condenser as a

result of dirt in the

fins

1

2

E

Alarm

Temperature of the

condenser is low-

ered and the fins of
the heat exchanger

are cleaned

ON/OFF

RESET

Alarm

ON/OFF

RESET

Programming process

Permanent shutdown

For environmental safety reasons, the chiller may only
be disassembled by authorised service centres.
REMKO GmbH & Co. KG or your contract partner would
be happy to provide you with the name of a service cen-
tre in your area.