beautypg.com

Condensation connection, External condensation pump – REMKO RKV 10 W User Manual

Page 15

background image

15

Electrical connection of the units:

Red

White

Orange

Yellow-
Green

Terminal strip

outdoor part

To the compressor
contactor

Protective conductor

Terminal strip

power supply

Terminal strip

indoor unit

A

N

2

L1

N

A

N

2

PE

PE

PE

Control
conductor

Neutral conductor

Outer conductor

230 V~,
50 Hz,
L1
N
PE

2 % incline

à

Always use suitable hose clips.

à

If the condensation is being guided to a drainage
line, please install a siphon-like hose guideway which
acts as an odour seal.

à

After the hose has been laid, check to make sure
that condensation can drain freely.

à

Make sure there is an adequate
incline for drainage.
It must be at least 2 %!

à

If the supplied condensation
hose is not long enough, it can
be attached to standard hoses
with a 17 mm inner diameter.

Condensation Connection

Condensation forms on the plate fin exchanger of the
indoor unit during cooling operation because tempera-
tures below the dew point are reached.
The indoor unit is equipped with a collection tray and a
condensation hose for the condensation that accumu-
lates.
Follow the instructions below to lay the condensation
hose:

à

The condensation drainage line is generally placed in
the same guideway as the refrigerant lines.

à

If, as a result of structural design conditions, it is
necessary to have a different guideway for the con-
densation hose, the hose can also be guided to the
indoor unit through a different drain.

à

If the unit is being operated at outside temperatures
below 0°C, the lines must be placed in such a way
that they are protected from frost.

External Condensation Pump

The condensation pump which can be purchased as an
accessory (Ref. no. 1613167) transfers the condensa-
tion which accumulates in the indoor unit to drains that
are placed in inconvenient locations, even if the drain is
located above the unit. The pump can be installed in-
side the unit.
Follow the operating instructions for the pump as well as
the instructions below:

à

Protect the housing from coming into direct contact
with the condensation.

à

Never open the housing of the pump.

à

Check the operating current of the pump and the
power supply for consistency.

à

Use the alarm contact to switch off the outdoor part.

à

Keep in mind that you should only use the alarm
contact together with a contactor or relay to switch
off the outdoor part, depending on the load.

à

Connect the pump securely to the control line.

Pump

The pump is attached to the right side of the unit (seen
from the back) using the supplied, self-adhesive strips.

Reservoir

Pump

Reservoir with sensor

The reservoir collects the condensation. A sensor
switches the pump on when a specific water level has
been reached.
The electronic sensor allows the reservoir to be rotated
by up to 30° on its axis.

Possible assembly positions:
Rotation of the axis up to 30°
to the right and left.

The condensation pump consists of 2 components:

à

The reservoir with sensor

à

The pump

6. Connect the unit to the current-free line from the out-

door part.
See figures.

7. Reassemble the unit.

This manual is related to the following products: