beautypg.com

Installation – REMKO RKV 10 W User Manual

Page 12

background image

12

Attaching the wall mount

The unit wall mounts are attached with screws and dow-
els suitable for attachment.

Installation

Make absolutely sure to follow the instructions below
prior to assembling the indoor unit:

à

When assembling the indoor unit, make sure that the
required minimum distances are observed.

à

Assemble the indoor unit in such a way that conden-
sation drainage is not blocked and air can always
flow freely in and out of the unit.

à

The indoor unit is attached by means of a wall
mount.

120

120

120

120

1500

Dimensions in mm

These safety zones ensure that air can flow freely in
and out of the unit, that maintenance and repair work
can be performed and to protect the unit from damage.

Minimum distances for the indoor units

The figure below shows the required distances to ensure
that the indoor units function properly.

RKV 24 W

Front view, all specifications in mm

240

107

36

Lead-through options

Prior to installation, take a look at the various options for
lead-throughs of the refrigerant, condensation and con-
trol lines (see figure below).

4

3

2

1

5

Units RKV 10 W, RKV 13 W and RKV 18 W can be
connected using all five options while the RKV 24 W
units can only be connected using options 1 to 3.

1 Outflow on the wall right 2 Outflow through the wall right
3 Outflow on the wall bottom 4 Outflow through the wall middle
5 Outflow on the wall left

Assembling the indoor unit

Installation is performed as follows:

1. The required line cross-sections are provided in the

"Technical Data” table.
Only use refrigerant lines with refrigerator quality.

2. Decide on a drainage option for the indoor unit and

cut the refrigerant connection line hose accordingly.

3. When assembling the unit, observe the bending radii

of the refrigerant lines and never bend the hose in
the same place twice.
This may cause the line to become brittle or crack

4. Remove the preinstalled swivel nuts of the units.
5. Keep in mind that the indoor units have been filled

with dry nitrogen as a sealant at the factory.
The pressurised nitrogen is released when the
swivel nuts are loosened.

Only use the swivel nuts supplied for further as-
sembly.

RKV 10 W / 13 W / 18 W

320

1000

midddle of the unit

5

160

240

200

200

35

500

Front view, all specifications in mm

This manual is related to the following products: