beautypg.com

REMKO RKV 10 W User Manual

Page 13

background image

13

uneven

thickness

formation

of cracks

formation

of cracks

rippled

CORRECT

9. Make sure that the flare has the correct shape.

Only tools approved for use in cold conditions may
be used.

Deburrer

Refrigerant line

Flare tool

If the length of the connection line is longer than 5
m, refrigerant must be added to the system during
initial operation.
See the section Adding Refrigerant.

Counterpressure

open-end wrench 1

Counterpressure

open-end wrench 2

10. First manually connect the refrigerant lines with the

shut-off valves and the bolts to ensure that they are
in the proper position.

11. Now tighten the bolts using 2 open-end wrenches

that have a large enough opening.

12. Use a second wrench to apply counterpressure

when tightening.

Oil recirculation

If the outdoor part is set up at a higher level than the in-
door unit, appropriate steps must be taken for oil recir-
culation.

Radius:
50 mm

Outdoor part

maximum

10 m

Indoor unit

Oil elevation arc in the
suction line to the outdoor
part 1x for every 2.5 m

This is usually accomplished by creating an oil elevation
arc that is installed every 2.5 meters of line going up.

6. Use only the tools below for assembly.

15. If you have selected Option 2 or 4 (drainage through

the wall), guide the condensation water and control
line through the wall lead-through to the indoor unit.
If you also need a condensation pump, it must be in-
stalled beforehand.

16. If, due to structural design conditions, it is not possi-

ble to guide the condensation line through as well,
make sure that the condensation can drain freely at
all times.

17. Hang the indoor unit leaning slightly to the back in

the previously assembled wall mount and press the
bottom of the unit into the mount.

18. Lay the refrigerant lines from the indoor unit to the

outdoor part.

19. Make sure that the refrigerant lines are adequately

secured.

20. Take steps, if necessary, to ensure oil recirculation

as described in the section on oil recirculation.

21. Place the control line in the same line guideway.
22. Remove the protective caps supplied and the swivel

nut caps of the shut-off valves and use these for
continued assembly.

23. Connect the refrigerant lines to the outdoor part as

described above.

7. Before you flare the refrigerant lines, ensure that

there is a swivel nut on the hose.

8. Work with the refrigerant lines as shown in the figure

below.

13. Insulate the installed refrigerant lines including the

connector against heat.

14. Only use insulation hoses sealed against diffusion

that are suitable for this temperature range.

This manual is related to the following products: