Test run

1.� Remove the �over�� from the

Remove the �over�� from the
valve��.�

2.� Start initial operation by briefly

Start initial operation by briefly
opening the blo�king valve��
on the outdoor unit until the
manometer indi�ate�� a pre����ure
of approx.� 4 bar.�

3.� Che�k all �onne�tion�� for leak��

Che�k all �onne�tion�� for leak��
u��ing leak dete�tion ��pray or
appropriate equipment.�

4.� �f you have identified any leak��,

�f you have identified any leak��,
open the blo�king valve�� by
turning them a�� far a�� po����ible
anti�lo�kwi��e u��ing a hexagonal
wren�h.�

�f leak�� are identified, the
defe�tive �onne�tion ��hould be
repla�ed.� �t i�� then e����ential to

�t i�� then e����ential to

�t i�� then e����ential to

repeat va�uum generation and
drying.�

5.� Turn on the on-��ite ma��ter

Turn on the on-��ite ma��ter
��wit�h or fu��e.�

6.� Set the target temperature on

Set the target temperature on
the indoor unit to a lower tem-
perature than the �urrent room
temperature u��ing the remote
�ontrol.�

7.� Swit�h the indoor unit to �ool-

Swit�h the indoor unit to �ool-
ing mode.�

9.� Che�k the �ontrol of the indoor

Che�k the �ontrol of the indoor
unit u��ing the fun�tion�� de-
���ribed in the operating manu-
al:
timer, temperature ��etting�� and
all mode ��etting��.�

10.� Mea��ure overheating, the

external, internal, outlet and
evaporation temperature�� and
enter the mea��ured data in the
initial operation log.�

11.� Remove the manometer and

re-atta�h all part�� previou��ly
removed.�
Make ��ure that the ��eal�� are
fitted in the �over��.�

Final measures

■�

Re-fit all part�� removed.�

■�

�n��tru�t the operator in how to
u��e the ��y��tem.�

8.� During the te��t run, �he�k the

During the te��t run, �he�k the
fun�tion and �orre�t ��etting
of all regulating, �ontrol and
��afety devi�e��.�

Dimen��ion�� and de��ign ��ubje�t to modifi�ation�� in the �our��e of te�hni�al development.�

Unit dimensions