NOTICE: If your installation does

not meet the minimum clear-

ances shown, you must do one

of the following:

• operate the logs only with the

flue damper open

• raise the mantel to an accept-

able height

• remove the mantel

FLOOR CLEARANCES

A. If installing appliance on the floor level, you

must maintain the minimum distance of 14"

to combustibles (see Figure 8).

B. If combustible materials are less than 14" to

the fireplace, you must install appliance at

least 5" above the combustible flooring (see

Figure 9).

INSTALLATION

Continued

Figure 8 - Minimum Fireplace Clearances

If Installed at Floor Level

Figure 9 - Minimum Fireplace Clearances

Above Combustible Flooring

Hearth

5"

Min.

Combustible

Material

14"

Min.

Combustible

Material

Noncombustible Material

Noncombustible Material

INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION

Note:

When used as a vented heater, appliance

must be installed only in a solid-fuel burning

fireplace with a working flue and constructed of

noncombustible material.
If your heater is a manually-controlled model, you may

use this heater as a vented product. There are three rea-

sons for operating your heater in the vented mode.
1. The fireplace does not meet the clearance to com-

bustibles requirements for vent-free operation.

2. State or local codes do not permit vent-free

operation.

3. You prefer vented operation.
If reasons number 1 or 2 above apply to you, you

must permanently open chimney flue damper. You

must install the damper clamp accessory (to order,

see Accessories, page 27). This will insure vented

operation (see Figure 10). The damper clamp will

keep damper open. Installation instructions are

included with clamp accessory.
See chart below for minimum permanent flue

opening you must provide. Attach damper clamp

so the minimum permanent flue opening will be

maintained at all times.

Area of Various Standard Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

Figure 10 - Attaching Damper Clamp

Masonry Fireplace

Chimney

Minimum Permanent

Height (ft.)

Flue Opening (sq. ins.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

Damper

Manufactured Fireplace

Damper Clamp

Damper

Damper
Clamp

Damper