REMKO RVS 60 H User Manual

Page 27

background image

Power supply

The system requires a fixed three
phase alternating current connec-
tion. The mains connection is to be
connected to the L1, L2, L3, N and
PE terminals.

We recommend the use of safety
fuses.

NOTE

Check all plugged and
clamped terminals to confirm
they are seated correctly and
make a permanent contact.
Tighten as required.

!

CAUTION

External enable contact ID5
Power on/ Stand-By

In addition to being operated with
the central controller or the cabled
remote controller, the system can
be switched on (normal mode) and
off (Stand-By) over an external
enabling contact.
For this the controller must be pro-
grammed (Figure 8) (see section
“Configuration external enabling
contact).

This contact is used for example
for Stand-by at night or activated/
deactivated from a building man-
agement system (BMS).

Proceed as follows to connect

power

1. Open the control panel and

switch cabinet cover by

removing the screws, lift off

cover.

2. Feed the dead cable through

the conduits into the switching

cabinet and clamp the cable to

the relive strain

3. Then connect the cable in ac-

cordance with the connection

diagram.

4. Check that the poles are con-

nected correctly.

5. Replace all parts which were

short-term

short-term

short-term

min. 5 sec.

+

...

...

repeated

short-term

short-term

short-term

short-term

External enabling contact

As manufactured in the factory, the system is switched on and off manu-

ally using the key-pads on the central controller or cable remote control.

If an external switch on and off is required the parameters must

be changed and the switch connected between terminals 28/29 and

29/30.
factory setting:

H 07 = 00 (manual switching on the controller)

possible change: H 07 = 01 (external switching)
After switching, with
- shortened terminals 28/29 and 29/30, the system is switched on.

- opened terminals 28/29 and 29/30, the system is switched off.
Operating using the unit´s controller is no longer possible once the

parameters have been changed.

8 External potential free contacts

28-29 / 29-30 Enabling contact on / Stand-By

(potential free) ID5

30-31 / 31-32 Operation contact cool/heat

(potential free) ID2

32-33 / 33-34 External fault contact

(max. 230V~, 3A)

Unit

User

Enable contact

General fault signal

Switching C-H

RVS RVS

100/150 60/75

27