Overview of the operating structure – REMKO RVS 60 H User Manual
Page 13
Overview of the operating structure
H01: Configuration unit
H02: Number of cycles
H03: Number of evaporators
H04: Number of compressors per cycle
H05: Configuration circulation pump
H06: Digital input cooling/heating
H07: Digital input On/Off
H08: Configuration controller
H09: Key lock controller
H10: serial address controller
H11: Configuration digital outlets
H12: Configuration 4-way reversing valve
r01: Target value cooling
r02: Hysteresis cooling
r03: Target value heating
r04: Hysteresis heating
r05: Rotation compressor 1/2
r06: Configuration compressor mode
r08: max. activation time compressor
r09: min. activation time compressor
r10: max. deactivation time compressor
r11: min. deactivation time compressor
r12: Hysteresis deactivation compressor
r24: Target value autom. Switching
r25: Target value AT deactivation compressor
r26: Target value dehumidification cooling
r27: Regulation medium volumes
r28: Minimum mode compressor medium K
r29: Hysteresis compressor medium K
r30: Minimum mode compressor medium H
r31: Hysteresis compressor medium H
r32: Target value "Hot start"
r33: Hysteresis "Hot start"
t01: Real time setting hour
t02: Real time setting minute
t03: Real time setting day
t04: Real time setting month
t05: Real time setting year
t06: Setting hour start cooling
t07: Setting minute start cooling
t08: Setting hour stop cooling
t09: Setting minute stop cooling
t10: Setting hour start heating
t11: Setting minute start heating
t12: Setting hour stop heating
t13: Setting minute stop heating
t14: Setting hour start LN cooling
t15: Setting minute start LN cooling
t16: Setting hour stop LN cooling
t17: Setting minute stop LN cooling
t18: Setting hour start LN heating
t19: Setting minute start LN heating
t20: Setting hour stop LN heating
t21: Setting minute stop LN heating
P01: Delay flow monitor before start
P02: Delay flow monitor mode
P03: Delay ND
P05: Fault reset
P06: Icon cooling/heating /
P08: Configuration dig. Input 1
P09: Configuration dig. Input 2
P13: Configuration input B4
P15: Configuration ND
P16: Fault excess temperature
P17: Delay excess temperature
P19: Fault insufficient temperature
P20: Configuration operating start
P21: Configuration fault relay
P22: Delay ND heating
P23: Delay ND defrosting
P25: Configuration dig. Output 2
P26: Configuration dig. Output 3
P27: Configuration dig. Output 4
P28: Configuration dig. Output 5
P34: Configuration dig. Input 5
P35: Deactivation fault relay via
P36: Configuration HD
01: sensor type B1
02: sensor type B2
03: sensor type B3
04: sensor type B4
13. Calibration B1
14. Calibration B2
15. Calibration B3
16. Calibration B4
21: Digital filter
22: Input limit
23: Unit of measurement °C/°F
A01: Target value frost protection
A02: Hysteresis frost protection
A03: Time delay frost protection
A04: Target value medium heating
A05: Hysteresis medium heating
A06: Sensor medium heating
A07: min. frost protection setting
C01: min. working time compressor
C02: min. down time compressor
C03: Time delay On-On compressor
C04: Time delay On-On compressor 1/2
C05: Time delay Off-Off compressor 1/2
C06: Switch-on delay compressor
C07: Switch-on delay pump-compressor
C08: Switch-off delay compressor-pump
C09: max. working time compressor step 1-2
C10: Working time compressor 1
C11: Working time compressor 2
C12: Working time compressor 3
C13: Working time compressor 4
C14: Maintenance fault compressor
C15: Working time circulation pump 1
C16: Working time circulation pump 2
C17: min. stop time before operation circulation pump
C18: min. working time circulation time
C19: Delay 4-way valve - compressor
d01: Function mode defrosting
d02: Input parameter °C/P
d03: Target value defrosting start
d04: Target value defrosting end
d05: min. working time defrosting start
d06: min. defrosting duration
d07: max. defrosting duration
d08: Delay defrosting interval cycle 1
d09: Delay defrosting interval cycle 1-2
d10: external contact defrosting start
d11: Frost protection heating
d12: Wait time before defrosting
d13: Wait time after defrosting
d14: Defrosting cycle 2
d15: Defrosting start cycle 2
d16: Forced ventilation time after defrosting
d17: Target value air circulation defrosting
d18: max. exterior temperature (slid. defr.)
d19: Hysteresis defrosting start (slid. defr.)
d20: Hysteresis exterior temperature (slid. defr.)
F01: Configuration fan output
F02: Operating mode fan
F03: min. initial speed
F04: max. initial speed
F05: Target value cooling mode °C/P
F06: Hysteresis value cooling mode °C/P
F07: Hysteresis min speed cooling
F08: Target value heating mode °C/P
F09: Hysteresis heating mode °C/P
F10: Hysteresis min speed heating
F11: Fan start-up period start with 100%
F12: Pulsing fan start-up period
F13: Function mode fan defrosting
F14: Pre-ventilation cooling
F15: Low noise activation
F16: Hysteresis low noise mode cooling
F17: Hysteresis low noise mode heating
b01: Current value sensor medium intake B1
b02: Current value sensor medium output B2
b03: Current value sensor condenser B3
b04: Current value HD-pressure transducer B4
Configuration
Password
Display
Display
Parameter value
Display
Password level
Current values
sensors
Compressor
Defrost
Fan
Units
Faults
Controller
Software
version
Real time clock
(not usable)
Frost protec-
tion
min. 5 sec.
short-term
short-term
+
/
Password level
Display
Direct / without PW
_d_
User / partly special
_U_
Superuser / special
_S_
Factory / manufacturer
_F_
13